The contactor interface type defaults are as follows:

DCN01 = CN1
DCN02 = CN2
DCN03 = CN3
DCN04-DCN08 = CN4

STC- Slope Thermal Compensation

Related

Commands

obj,attr

Description

sta

cha

ope

type

Range of Values

sc1,ide

Identifier

Text

SC1

sc1,des

Description

Text

Slope Thermal Comp

sc1,stt

State

number

0=disable 1=enable

sc1,rve

Raise Voltage Enable

number

0=disable 1=enable

sc1,fse

Probe Fail-Safe Enable

number

0=disable 1=enable

sc1,ltt

Lower Temperature Threshold

number

-5-20

°C or 23-68°F

sc1,ntt

Nominal Temperature Threshold

number

15-30

°C or 59-86°F

sc1,utt

Upper Temperature Threshold

number

30-55

°C or 86-131°F

sc1,spt

Step Temperature

number

45-85

°C or 113-185°F

sc1,lsp

Low temperature slope

number

1-10mV/

°C per cell

sc1,usp

Upper temperature slope

number

1-10mV/

°C per cell

INP- Input Management

Related

Commands

obj,attr

Description

sta

cha

ope

type

Range of Values

inmnn,ide

Identifier

number

m=module
nn=input number
Examples:
IN001=input 1 on controller
IN103=input 3 on module
with ID 1

inmnn,des

Description

text

See table below

inmnn,sn

Serial Number

text

Serial number

inmnn,brc

Board Code

text

Board code

inmnn,stt

Input state

text

0=not alarming 1=alarming

inmnn,typ

Input alarm type

text

"" – no alarm, for in006, this

value allows the input to
be used for either group
standby or PBT.

Polarity is ignored.

"FAN1" - drives FAN1 alarm
"FAN2" – drives FAN2
alarm
"FAJ1" – drives FAJ1 alarm
"FAJ2" – drives FAJ2 alarm
"OSA1" – drives OSA1
alarm
"AMJ1" – drives AMJ1

alarm, not valid for
NE872 or other LVD
card inputs.

Advertising