System-plant configuration, System-shelves configuration, Enable imminent lvbd shutdown – GE Industrial Solutions Galaxy Pulsar Edge User Manual

Page 79: System

Advertising
background image

Galaxy Pulsar Edge Power System Controller


Issue 3 October 2011

79

System Configuration Pages

System-Plant Configuration
Items in the section shown below are thought of plant level configurations. The ability to assign
the different alarm events severities, relays (if present), and to the LED is provided. Alarm events
can be assigned Critical (CRIT), Major (MAJ), Minor (MIN), Warning (WRN), or Record Only
(RO) severities. Submit must be used to save the changes.

Site ID

Up to 20 configured characters can be entered for the Site Identification.

Site Description

Up to 55 characters can be entered here for the Site Description.

Enable Imminent
LVBD Shutdown

When enabled, the Imminent Shutdown Alarm is generated prior to
opening the LVBD. Once the LVBD threshold has been reached, the
alarm is generated. The alarm is issued 15 seconds prior to opening the
contactor to provide an indication that system shutdown is imminent
due to a system battery disconnect. The alarm is based on the configured
LVBD battery disconnect threshold. The factory default for this feature
is Disabled.

Critical Equals
Major

Asserts the Critical alarm severity with all Major alarms.

System-Shelves Configuration

Items in the section shown below are used to define the physical attributes of the system
or plant. This includes the number of bays/frames, number of shelves per bay/frame,
whether the bay/frame has a door and if the controller is located on the door, and the shelf
width. It also provides the ability reserve positions in the shelf for specific components
like distribution so that the system can be depicted on the Home page. Adding a