Galaxy Pulsar Edge Power System Controller


Issue 3 October 2011

126

8 QS871A Remote Distribution

Monitor and Control Module

Overview

Although the Pulsar Edge has the ability to directly control and manage a single LVD contactor
without additional hardware. It can manage additional LVDs and distributions through the use of
remote distribution monitor and control modules like the QS871. The QS871A (CC109103371)
allows the Pulsar Edge controller to obtain distribution data and manage a non-latching contactor
through serial communications over the RS485 bus. The system controller monitors alarms for
open load or battery protectors, measures load or battery shunts, monitors the bus voltage, and
controls and monitors a single load or battery LVD contactor. Figure 8-1 shows the connections
and interfaces for the QS871A.

Figure 8-1: QS871A Remote Distribution Module

Features

The QS871A module has the following features:

Status LED: This is a tri-colored LED and will illuminate accordingly for the conditions

shown below.

LEDs ( = On)

Green

Amber

Red

Condition

Normal

Minor Alarm

Major Alarm

Flashing

Communication Loss with Controller

Flash (5s)

Manual Reconnect Command Accepting