GE Industrial Solutions Galaxy Pulsar Edge User Manual

Page 150

Advertising
background image

Galaxy Pulsar Edge Power System Controller


Issue 3 October 2011

150

obj

Description

CNO4

LVLD 3 Open

COF1

Queue Overflow

COR1

No Call-Out Response

DID1

ID Conflict

EMD1

Energy Management Disabled

EPO1

Emergency Power Off

EPR1

External Password Reset

EXL1

Excessive Login Attempts

FAJ1

External Fuse Major

FAN1

External Fuse Minor 24V

HCL1

History Cleared

ICR1

Incompatible Rectifier

ISD1

Imminent Low V Shutdown

LSF1

Load Share Fail

MAN1

Manual Off

MCM1

Major Communication Fail Alarm

MDP1

Voltage Duplicate ID

MZD1

Voltage ID Not Configured

NNC1

Unconfigured Alarm Destination

OSA1

Open String

PFD1

Password At Default

PFS1

Thermal Probe Fail Safe

PGI1

Program Line Invalid

PHT1

Processor Halt

POR1

No Dial-Out Response

RFA1

Rectifier Fail

RFN1

Rectifier Fan Fail

RIF1

Rectifier Internal Fault

SCD1

Battery Voltage Imbalance

STF1

Self Test Failed

TPA1

Thermal Probe Failure

VMF1

Voltage Channel Failure

VSF1

Sense/Control Fuse

ZID1

ID Not Configured

RMN-Rectifier Management

Related

Commands

obj,attr

Description

sta

cha

ope

type

Range of Values

gm1,ide

Identifier

Text

GM1

gm1,des

Description

Text

Rectifier Manager 1

gm1,lse

Load Share Enable

number

0=disable 1=enable

gm1,rme

Redundancy monitor enable

number

0=disable,1=enable

gm1,fsd

Float High Voltage Shutdown

number

25-30 or 50-60 V

gm1,bsd

Boost High Voltage Shutdown

number

26-30 or 52-60 V

gm1,fsp

Float Set-Point

number

22-28 or 44-56.5 V

gm1,bsp

Boost Set-Point

number

22-30 or 48-60 V

gm1,fcl

Float Current Limit

number

30-110%

gm1,bcl

Boost Current Limit

number

30-110%

gm1,oft

Oring FET Test Enable

number

0=disable 1=enable

gm1,wie

Walk-In Enable

number

0=disable 1=enable

Advertising