Status leds, Craft ports, Local and remote access ports – GE Industrial Solutions Galaxy Pulsar Edge User Manual

Page 47

Advertising
background image

Galaxy Pulsar Edge Power System Controller


Issue 3 October 2011

47

Status LEDs

The Pulsar Edge controller family provides two separate LED indicators that can be used to
provide a high level first glance local indication at the site of the status of the power system and
its monitored inputs. These LEDs can be configured to assist in providing more specific
indications of the system status. The LEDs provided are used to provide specific indication
concerning the system status as well as a separate indicator for an assigned alarm or alarms. The
alarm LED has factory assigned defaults as indicated in the table below. However, the
assignments to alarms can be customized in the field using the remote interfaces.

LED

LED Color

Status

Condition

System Or

Severity

Normal

Normal operation, no alarms, inputs and
outputs are in their normal range.

Critical
Alarm

Highest severity. Generally assigned to alarm
to indicate a Power affecting condition.
Immediate attention required.

Major Alarm

High severity. Generally assigned to alarm to
indicate a Power affecting condition.
Immediate attention required.

Minor Alarm

Medium severity. Generally assigned to alarm
to indicate a non-power affecting condition.
Attention eventually required.

Alarm

BD

Not
Illuminated

System above configured Battery on
Discharge (BD) threshold.

This state is not assigned by the present
default configuration.

System equal to or below configured Battery
on Discharge (BD) threshold.


Craft Ports

Local and Remote Access Ports

The Galaxy Pulsar Edge provides ports for both local and remote access. Access to these
ports depends on the specific Galaxy Pulsar Edge controller configuration. Various
versions of the Galaxy Pulsar Edge provide front access through a local DB-9 RS232
asynchronous serial port. Asynchronous RS232 connectivity is also available through an
RJ45 receptacle in specific controller configurations. A USB terminal connection is also
provided in specific controller configurations. The Galaxy Pulsar Edge’s integrated
Ethernet port can also be configured to and used for local craft port use. A standard RJ45
connection located is provided for access. Depending on the system, this connection can
be located at the rear or front of the shelf or system. Following are sample depiction of
these interfaces.