Galaxy Pulsar Edge Power System Controller


Issue 3 October 2011

115

Step

Action

4

Snap the cover closed on the VT-probe.

5

Place the first probe to the negative battery post as shown in figure.

6

The controller automatically recognizes the VT-probes. The number of registered
temperature probes and the highest battery temperature monitored may be checked
from the front panel by scrolling down the menu at MenuStatusBatteries. The
fields are “Num Temp Probes ()” and Highest Temp () where () contains the number of
devices communicating in the system as well as the highest battery temperature.

7

Connect either the 848719803 (5-ft) or the 848719811 (10-ft) cable to the 2-position
receptacle of the first probe and to the 3-position receptacle of another probe.

Verify the number of probes (2) registered with the controller with command:
MenuStatusBatteriesNUM TEMP PROBES (2)

8

Repeat Step 7 until all probes are installed.

9

The controller is now able to make thermal measurements in performing Slope
Thermal Compensation (STC). To enable or verify that STC is active go to
MenuConfigurationBatteriesBattery Temp Management and select TEMP
COMP
and verify that the feature Temperature Comp is Enabled. If not, configure and
save it appropriately. Additional parameters associated with slope thermal
compensation may be set on the controller to customize this feature.