Galaxy Pulsar Edge Power System Controller


Issue 3 October 2011

149

objid

Description

Threshold

rrtl1

Real-time reserve low

0-100hrs

rtl1

Reserve time low

0-100hrs

rls1

Redundancy Loss

1-87

vla1

Very low voltage

20-25.5 V

or 40-51 V



SDA- Alarms With No Threshold

Related

Command

obj,attr

Description

sta

cha

ope

type

Range of Values

objid,ide

Identifier

text

see below

objid,des

Description

text

see below

objid,fds

Front Panel Description

text

see below

objid,ast

Alarm state

number

0=not active 1=active

objid,sev

Alarm severity

text

CRIT, MAJ, MIN, WRN,
RO

objid,led

LED

text

BD,AC,DC,””

objid,acc

Contact Closure

text

R1,R2,R3,R4,R5,R6,R7,””

objid,dly

Notify Delay

number

0-540 seconds

objid,noo

Notify On Occur

number

0=no 1=yes

objid,nor

Notify On Retire

number

0=no 1=yes

objid,nag

NAG On Occur

number

0=no 1=yes

objid,dst

Notify Destination

text

“”, P1, P2, P3, P4, E1, E2,
E3, E4, S1, S2, S3, S4


obj

Description

AAC1

ACO Active

ACF1

AC Fail

AMJ1

Auxiliary Major

ATA1

Alarm Test Active

ATB1

Alarm Test Aborted

AUX1

Air Conditioner Fail

AUX2

Door Open

AUX3

High External Ambient

AUX4

Low External Ambient

AUX5

Fan Fail

AUX6

Hydrogen present

BBL1

Real Time Clock Battery Low

BFA1

Battery Test Failed

BTA1

Battery Test Active

CCH1

Configuration Changed

CLC1

Clock Changed

CLM1

Rectifier Current Limit

CMA1

Minor Communication Fail Alarm

CNF1

LVBD 1 Failed

CNF2

LVLD 1 Failed

CNF3

LVLD 2 Failed

CNF4

LVLD 3 Failed

CNO1

LVBD 1 Open

CNO2

LVLD 1 Open

CNO3

LVLD 2 Open