GE Industrial Solutions Galaxy Pulsar Edge User Manual

Page 21

Advertising
background image

Galaxy Pulsar Edge Power System Controller


Issue 3 October 2011

21

System Inputs/Outputs-Continued

Plant Current Measurement
Accuracy

0 to +50°C
-40 to +85°C

Resolution



±0.5% of full scale
±1.25% of full scale
1A

Temperature Measurement Accuracy
One-Wire Serial probes

-5 to +55°C
-40 to +85°C

Resolution



±1°C
±3°C
0.1°C

Environmental

General

Specification

Operating Temperature Range

-40 to 75°C (-40 to 167°F)

Storage Temperature Range

-40 to 85°C (-40 to 185°F)

Altitude

-200 to 13,000 feet (-61 to 3962 meters) See Note 1

Humidity

10% to 95% non-condensing

Audible Noise

< 60 dBA

Earthquake Rating

Zone 4, upper floors

Safety / Standards Compliance

Item

Specification

Safety Agency Approvals

Underwriters Laboratories (UL) Listed per Subject
Letter 1801: Power Distribution Center for
Communications Equipment, and cUL Certified (CSA
22.2 950): Safety of Information Technology
Equipment

European Economic Community (EEC)
Directives

EMC Directive 89/336/EEC, Low Voltage Directive
73/23/EEC as amended by Marking Directive
93/68/EEC

Radiated and Conducted Emissions

FCC Part 15, Class A
EN55022 (CISPR22), Class A

Electromagnetic Immunity

Meets Telcordia GR-1089-CORE

Electrostatic Discharge

EN61000-4-2 Level 1-4

RF Immunity

IEC61000-4-3 Level 3, 10 V/m

Conducted Immunity

IEC 61000-4-6 Level 3, Input Power Ports
IEC 61000-4-6 Level 2, Telecom Ports

Voltage Dips, Interruptions, and Variations

IEC 61000-4-11, EN55024 (CISPR24)


Note 1: For altitudes above 5000 feet (1524 meters), derate the temperature by 3.6 °F per 1000 feet
(0.656 °C per 100 meters).