ope dc1,stt=“boost”

The tables below summarize the object-attribute pairs in the system along with the commands
that can be used with the pair and the valid range that the attribute may have. The values in bold
text are the default settings for the attributes.

Objects, Attributes, and Related Commands

PSM- Power System

Related

Commands

obj,attr

description

sta

cha

ope

type

Range of Values

ps1,ide

Identifier

text

PS1

ps1,des

Power system description

text

≤ 32 characters

ps1,sid

Site ID

text

Up to 20 characters

ps1,sde

Site Description

text

Up to 55 characters

ps1,sys

System Description

text

Up to 55 characters

ps1,swv

Software version

text

d.d

ps1,verw

Web pages version

text

d.d

ps1,verb

Boot block version

text

d.d

ps1,verd

Display version

text

d.d

ps1,dflt

Defaults version

text

d.d

ps1,brc

Board code

text

“”

ps1,sn

Serial number

text

YYLLdddddddd

ps1,dow

Day of week

Text

Sunday…Saturday

ps1,dat

Date

date

format matching ps1,dtf

ps1,dtf

Date format

text

mm-dd-yyyy, dd-mm-yyyy,
yyyy-mm-dd

ps1,tim

Time

time

hh:mm

ps1,tmf

Time format

number

12, 24

ps1,dls

Daylight savings enable

number

0=disabled 1=enabled

ps1,tzo

Time zone offset

number

-840 - +840 minutes (±14
hours)

ps1,lng

Language

text

ENGLISH, OTHER
OPE changes the
descriptions

ps1,tun

Temperature units

text

C, F

Ps1,cem

Critical equals major

number

0=disable, 1=enable

ps1,fpc

Front panel configuration

number

0=disable, 1=enable

ps1,rrf

Remote rectifier off

number

0=disable, 1=enable

ps1,poe

Power off enable

number

0=disable, 1=enable

ps1,usl

Uninstall missing equipment

number

1

ps1,usr

Username enable

number

0=disable, 1=enable

ps1,dct

Display contrast

number

0 – 100 %

ps1,ptt

Communication port type

text

“LOCAL”,”MODEM”

ps1,amt

System ambient temperature

number

dd

°C

ps1,fst

Factory defaults

text

See ps1,fstl

ps1,fstl

Factory defaults list

text

Comma delimited list of
defaults

ps1,rap

Reset Passwords

number

1 = reset passwords (OPE
only valid from local