GE Industrial Solutions Galaxy Pulsar Edge User Manual

Page 197

Advertising
background image

Galaxy Pulsar Edge Power System Controller


Issue 3 October 2011

197

SEVERITY RELAY

USER RELAYS

LED

SNMP

Description

CRIT

PMJ

PMN

WRN

RO

R1

R2

R3

R4

ALM

DST

Object

ID

Major Communication Fail Alarm

MAJ

MCM1

Manual Off

MIN

MAN1

Minor Communication Fail Alarm

MIN

CMA1

Multiple AC Fail

MAJ

R3

MACF1

Multiple Converter Fail

MAJ

R2

CMFA1

Multiple Manual Off

MAJ

MMAN1

Multiple Rectifier Fail

MAJ

R2

MFA1

No Call-Out Response

WRN

COR1

No Dial-Out Response

WRN

POR1

Open String

MAJ

OSA1

Password At Default

RO

PFD1

Processor Halt

RO

PHT1

Program Line Invalid

MAJ

PGI1

Queue Overflow

WRN

COF1

Real Time Clock Battery Low

MIN

BBL1

Real-Time Reserve Time Low

RO

RRTL1

Rectifier Current Limit

RO

CLM1

Rectifier Fail

MIN

R2

RFA1

Rectifier Fan Fail

MIN

R2

RFN1

Rectifier Internal Fault

MIN

R2

RIF1

Redundancy Loss

MIN

R2

RLS1

Reserve Time Low

RO

RTL1

Self Test Failed

MIN

STF1

Sense Fuse

MIN

VSF1

Thermal Probe Fail Safe

MAJ

PFS1

Thermal Probe Failure

MIN

TPA1

Unconfigured Alarm Destination

WRN

NNC1

Un-powered Controller (Not
configurable)

x

x

x

Very High Battery Temperature

MAJ

BTVH1

Very High Voltage

MAJ

HVA1

Very Low Battery Temperature

MAJ

BTVL1

Very Low Voltage

MAJ

ALM

VLA1

Voltage Channel Failure

MIN

VMF1

Voltage Duplicate ID

MAJ

MDP1

Voltage ID Not Configured

MAJ

MZD1

Advertising