Galaxy Pulsar Edge Power System Controller


Issue 3 October 2011

160

Alarm Cut-off

Related

Commands

obj,attr

Description

sta

cha

ope

type

Range of Values

aco1,jae

Major Alarm Cut-off Enable

Number

0=disable 1=enable

aco1,jto

Major Alarm Cut-off Time-Out

Number

1 to 8 hours

aco1,nst

Minor Alarm Cut-off State

Number

0=inactive 1=active

aco1,nae

Minor Alarm Cut-off Enable

Number

0=disable 1=enable

aco1,nto

Minor Alarm Cut-off Time-Out

Number

1 to 72 hours

aco1,lbe

Local Buzzer Enable

Number

0=disable 1=enable



UDE- User Defined Events

Related

Commands

obj,attr

Description

sta

cha

ope

type

Range of Values

unnnn,des

Description

Text

30 char

unnnn,fds

Front Panel Description

text

see below

unnnn,ast

Alarm State

Number

0=inactive 1=active

unnnn,sev

Severity

Text

CRIT, MAJ, MIN, WRN,
RO

unnnn,prg

Program Line

Text

60 char

unnnn,dur

Minimum Duration

Number > 0 seconds

unnnn,lat

Latched

Number

0=no 1=yes

unnnn,led

LED

text

BD,AC,DC,””

unnnn,acc

Contact Closure

text

R1,R2,R3,R4,R5,R6,R7,””

unnnn,dly

Notify Delay

Number

0-540 seconds

unnnn,noo

Notify On Occur

Number

0=no 1=yes

unnnn,nor

Notify On Retire

Number

0=no 1=yes

unnnn,nag

NAG On Occur

Number

0=no 1=yes

unnnn,dst

Notify Destination

text

“”, P1, P2, P3, P4, E1, E2,
E3, E4, S1, S2, S3, S4

where nnnn = 1 thru 128




DRC-Derived Channels

Related

Commands

obj,attr

Description

sta

cha

ope

type

Range of Values

DRnn,des

Description

Text

30 char (Derived Chan nn)

DRnn,val

Value

Number

Number units

DRnn,prg

Program line

Text

60 char

DRnn,uni

Unit

Text

5 chars

Where nn is from 01 thru 8






TRS- Trend

Related

Commands

obj,attr

Description

sta

cha

ope

type

Range of Values

Obj,ide

Identifier

DCT1 for DC plant load