GE Industrial Solutions Galaxy Pulsar Edge User Manual

Page 168

Advertising
background image

Galaxy Pulsar Edge Power System Controller


Issue 3 October 2011

168

line is the end-of-command identifier. The “* ” in the example above is the user command line
prompt.

sum

Report Plant Load Trend Statistics

Syntax:

sum dct1

Description
This command reports the plant trend statistics, which includes up to 16 daily highest hourly
and lowest hourly instantaneous readings, up to 32 daily maximum hourly averages, and up to
13 monthly averages of the daily maximum hourly averages. The following is an example of a
command response:

* sum dct1
:DCT1
SRC=DC1 ADC
CLR=01-JAN-2001,12:00:00
DHI=
29-JAN-2002,02:00;00,123.2
30-JAN-2003,05:00:00,120.1
31-JAN-2003,14:00:00,122.8
DLI=
29-JAN-2002,12:00;00,120.9
30-JAN-2003,08:00:00,118.7
31-JAN-2003,01:00:00,119.2
DHH=
29-JAN-2002,02:00;00,122.1
30-JAN-2003,05:00:00,119.7
31-JAN-2003,14:00:00,121.6
MAV=
31-JAN-2003,23:00:00,121.3
.
*

The “DHI=” indicates daily highest hourly instantaneous reading. The “DLI=” indicates daily
highest hourly instantaneous reading. The “DHH=” indicates daily highest hourly average
reading. The “MAV=” indicates monthly average of daily highest hourly average reading. The
“.” line is the end-of-command identifier. The “* ” in the example above is the user command
line prompt.

sum

Report Battery Discharge Statistics (Profile)

Syntax:

sum dc1,bod

Description
This command reports the last battery discharge profile report. The report includes cleared date
and time, start date and time, end date and time, duration in seconds, and up to 50 sample
points. Each sample is time stamped in seconds. We compress the samples to derive a
minimum set of data required to reconstruct the curve while retaining important coup de fouet
minimum and maximum voltages and lowest voltage at end of discharge. The following is an
example of a command response:

* sum dc1,bod
:DC1 BOD

Advertising