Inventory, Battery discharge – GE Industrial Solutions Galaxy Pulsar Edge User Manual

Page 69

Advertising
background image

Galaxy Pulsar Edge Power System Controller


Issue 3 October 2011

69

Inventory

Battery Discharge

Provides a chronological view of up to the last 16 battery on discharge (BD) alarm events that
have occurred since the last time the history log was cleared. In addition, 300 points are used to
store battery discharge profiles. A typical discharge curve for a standard constant power load
utilizes about 30 points a curve. Selecting Battery Discharge from the reports screen produces
the following page.

The Battery Discharge History events provide date and time, average load during
discharge, and duration of each recorded battery discharge event. The reserve time will
be provided if available for each event. Selecting a color from the view data screen will
allow the discharge curve profiles to be graphed and overlayed.

Advertising