Galaxy Pulsar Edge Power System Controller


Issue 3 October 2011

76

Aborted, Redundancy Loss Alarm, and Converter Redundancy Loss.

Clear History

This operation is used to clear the various items that the controller
maintains history records. Once cleared the controller begins to keep
history of new events.

All History

Single command to clear all history.

Alarm History

Clears only alarm event history.

BD History

Clears only BD history.

Rectifier History

Clears only rectifier event history.

Boost History

Clears only Boost event history.

Local Port History Clears only local port access event history.
Modem History

Clears only Modem port access event history.

Network History

Clears only network access history.

Clear Statistics

This operation is used to clear the various items that the controller
maintains statistical records. Once cleared the controller begins to
keep new statistics.

All Statistics

Single command to clear all statistics.

Plant Load

Clears only plant load statistics.

Battery Discharge

Clears the Battery on Discharge (BD) statistics

kept on the plant load and voltage during
discharge.

Battery Temp

Clears only battery temperature statistics.

Trend

Clears only Trend statistics kept on the load.

Disconnects Maintenance Operations

Appropriate Buttons are provided to allow operation of LVDs when they are attached in
the system.

Open/Close LVBD

Provides individual manual control of Low Voltage Battery
Disconnect (LVBD) for maintenance purposes.

Open/Close LVLD1

Provides individual manual control of Low Voltage Load Disconnect 1
(LVLD1) for maintenance purposes.

Open/Close LVLD2

Provides individual manual control of Low Voltage Load Disconnect 2
(LVLD2) for maintenance purposes.

Open/Close LVLD3

Provides individual manual control of Low Voltage Load Disconnect 3
(LVLD3) for maintenance purposes.

Rectifier or Converter Start/Stop Maintenance Operations

The maintenance page in the Pulsar Edge provides a remote user the ability to place a
rectifier into Standby if the “Remote Rectifier In Standby”. A user has the ability to turn-
off (Stop) or turn-on (Start) a specific rectifier. These are based upon the position of the
buttons. G11 below has been placed into Standby and can be turned back on or started by
initiating the Start Rectifier for G11. Rectifiers G12 and G13 are On and producing
power. These rectifiers can be manually placed into Standby (Off) by performing the
Stop operation.