GE Industrial Solutions Galaxy Pulsar Edge User Manual

Page 196

Advertising
background image

Galaxy Pulsar Edge Power System Controller


Issue 3 October 2011

196

SEVERITY RELAY

USER RELAYS

LED

SNMP

Description

CRIT

PMJ

PMN

WRN

RO

R1

R2

R3

R4

ALM

DST

Object

ID

Auxiliary 12

MAJ

AUX12

Auxiliary Major

MAJ

AMJ1

Battery Test Active

RO

BTA1

Battery on Discharge (Float and Boost)

MAJ

R1

ALM

BDA1

Battery Voltage (Cell) Imbalance
Detect

MIN

SCD1

Check Battery/Battery Test Failed

MIN

BFA1

Clock Changed

RO

CLC1

Configuration Changed

RO

CCH1

Controller Fail (Not user mappable)

x

x

x

Converter Distribution Fuse

MAJ

R4

CDFA1

Converter Fail

MAJ

R2

CFA1

Converter Fan Fail

MIN

R2

CFN1

Converter Input Fail

MIN

CIN1

Converter Low Voltage

CRIT

CVLA1

Converter High Voltage Major

MAJ

CHVA1

Converter High Voltage Minor

MIN

CHFV1

Converter ID Conflict

MAJ

CDID1

Converter Redundancy Loss

MAJ

R2

CRL1

Emergency Power Off

MAJ

EPO1

Energy Management Disabled

WRN

EMD1

Excessive Login Attempts

WRN

EXL1

External Password Reset

WRN

EPR1

Fuse Major

MAJ

R4

FAJ1

Fuse Minor

MIN

FAN1

High Ambient Temperature

MIN

AMTH1

High Battery Temperature

MIN

BTHA1

High Voltage

MIN

HFV1

History Cleared

RO

HCL1

ID Conflict

MAJ

DID1

ID Not Configured

MAJ

ZID1

Imminent Low V Shutdown

MAJ

ISD1

Incompatible Converter

MIN

ICC1

Incompatible Rectifier

MIN

R2

ICR1

Load Share Fail

MIN

LSF1

Low Ambient Temperature

MIN

AMTL1

Low Battery Temperature

MIN

BTLA1

LVBD Failed

MAJ

CNF1

LVBD Open

MAJ

CNO1

LVLD 1 Failed

MAJ

CNF2

LVLD 1 Open

MAJ

CNO2

LVLD 2 Failed

MAJ

CNF3

LVLD 2 Open

MAJ

CNO3

LVLD 3 Failed

MAJ

CNF4

LVLD 3 Open

MAJ

CNO4

Advertising