GE Industrial Solutions Galaxy Pulsar Edge User Manual

Page 83

Advertising
background image

Galaxy Pulsar Edge Power System Controller


Issue 3 October 2011

83

Shunt

Type

System Configuration

Proposed Controller Operation

All battery management features shall
be available.

Shunt input may or may not be
connected to a shunt located in the
system. There are no “Shunt Monitors”
configured in the system.

Controller shall report the following:

I

Load

= Σ I

Rect

I

battery

= Unavailable








NONE


Shunt input may or may not be
connected to a shunt located in the
system. System has Shunt Monitors
configured in the system.

Note: even if not being used and
centralized shunt must be mounted in
the grounded side of the system’s DC
bus. Possible damage may occur if the
shunt is connected incorrectly.

1. If cards are configured to monitor

“Battery” shunts, it shall be
assumed that all battery current
flows through these shunts to and
from the system batteries and shall
be summed to be equivalent to the
total battery current ( I

battery

).

2. Cards configured as monitoring a

“Load” shunt shall not affect the
total I

Load

but have their values

individually displayed.

Thus, the controller shall report the
following:

I

battery

= Σ I

battery shunt monitors

I

Load

= Σ I

Rect +

Σ I

battery shunt

monitors

Where I

battery shunt monitors

is negative for

current into the battery and positive for
current out of the battery.
Note: If there are no Shunt Monitors
configured as battery then:

I

battery

= Unavailable

I

Load

= Σ I

Rect

Shunt input may or may not be
connected to a shunt located in the
system. System has Shunt Monitors
configured in the system and all system
loads are monitored.

And


The new “All Load Monitored” feature
has been “Enabled”.

1. Cards configured to monitor

“Battery” shunts are assumed to
monitor all battery current to and
from the system batteries and shall
be summed to be equivalent to the
total battery current ( I

battery

). In

addition, all individual battery
monitor values shall be displayed

2. Cards configured as monitoring a

“Load” shunt shall be summed to
calculate the total I

Load

and also

have their individual values
displayed.

Thus, the controller shall report the
following:

I

battery

= Σ I

battery shunt monitors

I

Load

= Σ I

Load shunt monitors

Note: If there are no Battery Shunt
Monitors configured but the total load