GE Industrial Solutions Galaxy Pulsar Edge User Manual

Page 68

Advertising
background image

Galaxy Pulsar Edge Power System Controller


Issue 3 October 2011

68

Site

Displays up to 20 configured characters entered for the Site
Identification.

Description

Displays up to 55 characters entered for the Site Description.

Primary Bus

Displays the values of the system rectifier DC output bus voltage and
output current (value to the load). The bus voltage is measure directly
by the Pulsar Edge. The load current displayed depends on the system
configuration and is either a calculated value, a value determined by
remote monitoring modules, or measured directly by the shunt monitor
on-board the Pulsar Edge.

Note: the shunt must be mounted in the grounded side of the system’s
DC bus. Possible damage may occur if the shunt is connected
incorrectly.

Secondary Bus

Displays the values of the system converter DC output bus voltage and
output current (value to the load). The bus voltage is measure directly
by the Pulsar Edge. The load current displayed depends on the system
configuration and is obtained by summing up the output values of the
individual converters.

State

Provides the present operating mode of the system. (Float, Boost)

Plant Type

Indicates the generic voltage classification of the power system: -48V,
+24V, +48V, etc.

Serial Number

The serial number of the installed Pulsar Edge Controller.

Date

Present Date of the Pulsar Edge on-board real-time clock using the
configured Date format.

Time

Present time of the Pulsar Edge on-board real-time clock using the
configured time format.

Ambient
Temperature

Value of temperature sensor embedded in the controller display. Meant
to provide a relative temperature.

At the top of this section are the controller name and code versions

.

Placing the cursor over the numbers in the () will provide the software version of the boot block,
application code, and web pages.

Reports Page

The Reports page provides Inventory, Battery Discharge History, Statistics, Trends, Alarm
History, Boost History, Login History, Rectifier History, and Converter History in report format.
Data is stored on a first in first out event storage scheme. Once the record size of a specific field
is reached the data first in will be discarded for the newer data. These screens are generally self-
explanatory. Following are sample screens from these tabs.