Backup/Restore Configuration File

Using any FTP client, perform the following steps to load default web pages:

1. Type: FTP x.x.x.x (The controller should have a Working IP Address of 192.168.2.1).

ftp 192.168.2.1
Connected to 192.168.2.1

220 841 FTP Ready


2. Login as guest using the using the network administrator password (administrator).

User (192.168.2.1:(none)): guest

331 User name okay, need password

Password: administrator

230 Logged in


3. Change directory (cd) to the config directory by typing: cd config.

ftp> cd config

250 CWD command successful


Backing Up/Retrieving


4. To retrieve a backup of a site’s configuration use the get command to get a copy of the
configuration file (config.gal).

ftp> get config.gal

200 Port command okay
150 Opening data connection for STOR (192.168.2.1,1576)
226 File sent OK

Restoring


4. To restore a backup of a site’s configuration use the put command to load a copy of the
configuration file (config.gal) to the site.


ftp> put filename config.gal
Note:
The full path of to the file with the filename must be provided. It is OK just
to use the same name with a command like the following:

ftp> put config.gal


200 Port command okay
150 Opening data connection for STOR (192.168.2.1,1576)

5. Verify the transfer by a message displayed indicating a successful file transfer.

226 File sent OK