Galaxy Pulsar Edge Power System Controller


Issue 3 October 2011

87

and +14:00 Hrs:Mins. NTP address must be provided and controller
rebooted for the Time Zone Offset to work properly.

The factory default is 0:00 Hrs:Mins

Enable Daylight
Saving

Enable or disable of automatic switch over with Daylight Saving.
The factory default is Enabled.

Temperature Units

Selects between displaying temperature measurement in °C or °F. The
factory default is °C.

Clock Battery Low

Automatic event generated by the controller when its internal lithium
battery is low. The severity of the alarm can be set as desired.

Clock Changed

Any change to the Date or Time is an Event the controller detects. The
severity of the alarm can be set as desired.

System-Alarm Test Configurations
When equipped with alarm output contacts, the Pulsar Edge provides a user the ability to
manually test the system alarm output contacts. Wiring to monitoring systems can be tested in the
field or factory using this feature. The duration of the alarm contact assertion can be configured
from 5 to 300 seconds. Specific relays may also be selected. Following is a sample Alarm Test
screen.

System-Branding/Styling Configurations
Pulsar Edge web pages contain references to the Lineage Power as well as the Pulsar Edge. These
can be removed from the web pages by configuring Company and Product Headings. Clicking on
the color wheels and pull-downs and trialing different colors is an effective way of using this
feature.

Advertising