csr,adc

DC Current

Number

Number in amps

csr,cap

Capacity

Number

Number in amps

csr,stt

State

Text

ON*, OFF, STANDBY*,
MISSING, VACANT*
ON qualifiers –LIM
OFF qualifiers –LVD, -INF,
-TA, -HVSD, -FAN

csr,cfa

Converter Fail

Number

0=inactive 1=active

csr,did

ID Conflict

Number

0=inactive 1=active

csr,ccf

Communication Fail

Number

0=inactive 1=active

s stands for shelf number (0 or 1)
r stands for converter number (1 thru 6)
* The user may only set the state to ON, STANDBY, or VACANT

BAR-Battery Reserve Management

Related

Commands

obj,attr

Description

sta

cha

ope

type

Range of Values

br1,des

Description

Text

Battery Reserve 1

br1,adc

Total battery current

number

d A (+ for discharge, - for
charge)

br1,hbt

Highest battery temperature

number

dd

°C

br1,lbt

Lowest battery temperature

number

dd

°C

br1,cap

Installed battery capacity

number

ddddd AH

br1,olcap

On-line battery capacity

number

ddddd AH

br1,btr

Discharge test results

text

result,reserve,load
result
is one of the following:
COMPLETED
CHECK BATTERY
INTERRUPTED
ACTIVE
NOT RUN
reserve is hours calculate by
last complete test
load is load at beginning of
test

br1,tth

High Temperature Threshold

Number

30-90

°

C or 86-194

°

C

br1,cle

Current Limit Enable

number

0=disable 1=enable

br1,clt

Current Limit Threshold

number

5-1000A

br1,cev

Battery string end of discharge V

Number

19.25-22.75V
or 40.25-43.75V

br1,bts

Battery Test State

number

0=inactive 1=active

br1,mtt

Manual test type

text

DISABLED, 20%, TIMED

br1,tev

Manual test alarm voltage

number

21-27V or 36-48 V

br1,tmd

Manual test duration

number

0.1-99.9 hours

br1,bte

Auto test type

text

DISABLED, 20%, TIMED

br1,btv

Battery test rectifier voltage

number

21-26 V or 42-52 V

br1,ath

Auto test start hour

number

0-23

br1,tin

Auto test interval

number

1-18 months

br1,atw

Auto test min hours after BD

number

0-240 hours

br1,atd

Auto test date

date

dd-mmm-yy

br1,nvm

Number of mid-cell V present