Galaxy Pulsar Edge Power System Controller


Issue 3 October 2011

163

ANET- Auxiliary Network Settings

Related

Commands

obj,attr

Description

sta

cha

ope

type

Range of Values

net2,dom

Static Domain Name

text

(not used if DHCP enabled)

net2,msrv

Mail host IP

IP
address

xxx.xxx.xxx.xxx (0.0.0.0
will force a DNS lookup of
“mailhost”)

net2 is currently only used by an attached Gateway Card in the NX400 system.


Additional T1.317 Commands and Samples

ala

Report Active Alarms

Syntax:

ala

Description
This command reports all the active alarm conditions in the plant. One alarm message is listed
per line in the report. The table below lists the default alarm messages. Note that if user
changes the severity of the alarm, the corresponding change will show up in the alarm message.
However, alarm conditions with the RO severity will not be displayed, the rec command,
discussed later, should be used.

Alarm Message
MAJ, Multiple Rectifier Fail
MAJ, Multiple AC Fail
MAJ, Battery On Discharge
MAJ, High Voltage
MAJ, Sense Fuse
MAJ, Fuse Major
MAJ, Auxiliary Major
MAJ, Contactor 1 Open
MAJ, Contactor 1 Fail
MAJ, Major Communication Fail
MAJ, High Battery Current Shutdown
MAJ, Shorted Cell Detected
MAJ, Imminent Low V Shutdown
MAJ, Open String

MIN, Rectifier Fail
MIN, AC Fail
MIN, Thermal Probe Fail
MIN, Battery High Temp
MIN, Rect Redundancy Loss
MIN, High Battery Current
MIN, Minor Communication Fail
MIN, Circuit Pack Failure
MIN, Mid-cell V Monitor Fail

If no alarms are active “NO ACTIVE ALARMS” is reported.