User defined events – GE Industrial Solutions Galaxy Pulsar Edge User Manual

Page 109

Advertising
background image

Galaxy Pulsar Edge Power System Controller


Issue 3 October 2011

109

Following is a sample screen of a CP841A_3C3R.


User Defined Events

This page provides the ability to create specific events using the T1.317 variables and the
basic mathematical operators to create a User Defined Event by creating a specific
program line. Once the event is created it has the very similar configurable attributes as
other basic controller alarms. Following is a sample screen.

Program Line

Sets the condition upon which the alarm will be asserted. The
program line can have total of 40 characters having a total of 12
operators and operands

Logical operators are:

& AND, | OR, ^ XOR and ! NOT

Binary mathematical
operators are:

+ plus, - minus, * times and / divide

Unitary mathematical
operators are

+ Positive, - Negative

Comparator operators
are:

= equal, < less than and > greater than. Parentheses are accepted