Reserve-battery types configurations, Reserve-voltage modules configurations – GE Industrial Solutions Galaxy Pulsar Edge User Manual

Page 93

Advertising
background image

Galaxy Pulsar Edge Power System Controller


Issue 3 October 2011

93

Factor

the time duration of Boost. The value can be set from .1 to 9 with a
factory default setting of .5.

Current Threshold

Configured battery current threshold during Boost that will end the
Boost operation and return the system back to Float. The value can be
set from 1 to 999 Amps with a factory default setting of 5 Amps.

Pages with Boost
Settings

Provides a quick link to other pages with configuration items
associated with Boost.

Reserve-Battery Types Configurations
Items in this section of the Settings pages are used to configure the various battery models and the
parameters associated with them. A maximum of 25 battery models can be stored in the
controller. Batteries can be added and deleted simply by clicking on the correct link. Adding a
battery requires a description of the battery model, the general technology class the battery falls
under, and the 8-hour to 1.75V amp-hour rating of the battery. A sample screen shot follows
along with parameter descriptions.

Reserve-Voltage Modules Configurations
Items in this section of the Settings pages are used to configure the various alarms and description
attributes for the ES771 mid-string voltage modules. Following is a sample screen from a system
with two ES771 modules.