Galaxy Pulsar Edge Power System Controller


Issue 3 October 2011

130

Note: The common or return of the micro switch for these signals shall be attached to Vbus- in
the system outside of this board.

J3

Connection that provides field access to External Auxiliary Fuse Alarm Major and the
Remote LVD input.

Pin # Signal Name

Signal Description

1

Remote LVD External contact closure for remote disconnecting attached LVD;

Disconnects LVD on a dry contact closure to Remote LVD Return
when feature is enabled.

2

Remote LVD
Return

Protective (PTC or resistive) return to NE common for External
Remote LVD contact closure input signal.

3

Aux_Alarm

General purpose Fuse Alarm Major (FAJ) alarm input; Major alarm on
closure to the non-grounded “Battery” side of the DC bus Battery (-
48V).

J100

and

J101

Provides connectivity to the RS485 GP rectifier/converter bus as well as a pass through
to the next RS485 connected device.

Pin # Signal Name

Signal Description

1

RS485+

B Inverting Driver Output / Inverting Receiver Input

2

RS485-

A Non-inverting Receiver Input/ Non-inverting Driver Output

3

RS485REF

RS485 Reference/return. Pass-through on this board.

4

No Connection

5

-

Connects between J101.5 and J100.5. Connection reserved for1-Wire
communication signal in the system.

6

-

Connects between J101.6 and J100.6. Connection reserved for1-Wire
+5V signal in the system.

7

No Connection

8

No Connection


Note: if these boards are to be used in custom configuration design consideration must be
given to the selection of the non-latching contactor as well as thermal considerations
when mounting the board. This board requires heat sinking and other thermal
management techniques.