Installation - minimum configuration, Installation – GE Industrial Solutions Galaxy Pulsar Edge User Manual

Page 110

Advertising
background image

Galaxy Pulsar Edge Power System Controller


Issue 3 October 2011

110

Installation - Minimum Configuration

This section provides the minimum configuration required to get a site configured. It
includes the Site ID (up to 12 characters), Site Description (Up to 55 characters), Date,
Time, and the installed battery type. The “J-Code” for the shelf is used by the controller
to define the web page view of the auxiliary inputs and generally should not be edited
when the product is shipped from the factory. A high level summary of the basic installed
equipment is also provided.

Enable Walk-In

Standard system applications generally will always have system level
rectifier Walk-In Enabled. There is a small subset of applications,
generally not involving batteries that do not desire the typical telecom
system rectifier walk-in characteristics. By not selecting the controller
will issue a command to the rectifiers to disable walk-in. Once the
command has been sent power to all the rectifiers must be cycled in
order for their new mode of operation will take hold. Presently only
versions of the Compact Power Line (CP) rectifiers have this
capability. The overwhelming majority of systems will use the walk-in
mode of operation. When in doubt, contact your local technical field
support.

The factory default for this feature is Enabled (checked).

ID Override

Standard systems from the factory are designed such that rectifiers
report their individual shelf and slot locations to the controller in the
form of an ID (Gxy). “x” is the shelf ID and “y” is the slot position in
that shelf. There are some custom systems that exceed the normal ID
addressing scheme. To work with these systems the typical ID
addressing scheme must not be used and be overridden. Checking this
box enables that feature. Shelf and slot positional information is lost
when operating in this mode. The vast majority of systems will not use
this mode of operation. When in doubt, contact your local technical
field support.

The factory default for this feature is disabled (not checked).