GE Industrial Solutions Galaxy Pulsar Edge User Manual

Page 159

Advertising
background image

Galaxy Pulsar Edge Power System Controller


Issue 3 October 2011

159

LPT -Local RS-232 Port

Related

Commands

obj,attr

Description

sta

cha

ope

type

Range of Values

4800, 9600, 19200

lp1,dbt

Data Bits

Number

7, 8

lp1,pry

Parity

text

O, E, N

lp1,sbt

Stop Bits

Number

1, 2

lp1,tmo

Time-Out

Number

0(disabled) – 45 minutes

lp1,hsh

Handshaking

text

NO, HW, SW

lp1,app

Application

Text

TERMINAL, EVENT LOG
(HW,SW)

lp1,wre

Write Enable

Number

0=disable 1=enable
(HW,SW)


ATS- Alarm Test

Related

Commands

obj,attr

Description

sta

cha

ope

type

Range of Values

at1,des

Description

Text

Alarm Test 1

at1,stt

Alarm Test State

Number

0=inactive 1=active

at1,stg

Alarm Test Stage

text

PCR,PMJ,PMN,R1,R2,R3,R
4,R5,R6,R7

at1,lte

Alarm Test Enable

Number

0=disable 1=enable
(HW,SW)

at1,dur

Duration

Number

5-300 seconds

at1,pmj

Test Power Major

Number

0=no 1=yes

at1,pmn

Test Power Minor

Number

0=no 1=yes

at1,r1

Test Relay 1

Number

0=no 1=yes

at1,r2

Test Relay 2

Number

0=no 1=yes

at1,r3

Test Relay 3

Number

0=no 1=yes

at1,ets

Email Test

number

1=do test (sets and clears
ATA1)

at1,ems

Email Results

text

at1,bzi

Audio Test Duration

Number

5-300 seconds

at1,bzt

Audio Test State

Number

“”=Stop Test, Local=local
buzzer

at1,irt

Individual Relay Test State

Number

“”=Stop Test,
PCR,PMJ,PMN,R1,R2,R3,R
4,R5,R6,R7



Alarm Cut-off

Related

Commands

obj,attr

Description

sta

cha

ope

type

Range of Values

aco1,des

Description

Text

Alarm Cut-off 1

aco1,stt

Alarm Cut-off State

Number

0=inactive 1=active

aco1,cst

Critical Alarm Cut-off State

Number

0=inactive 1=active

aco1,cae

Critical Alarm Cut-off Enable

Number

0=disable 1=enable

aco1,cto

Critical Alarm Cut-off Time-Out

Number

1 to 8 hours

aco1,jst

Major Alarm Cut-off State

Number

0=inactive 1=active

Advertising