GE Industrial Solutions Galaxy Pulsar Edge User Manual

Page 165

Advertising
background image

Galaxy Pulsar Edge Power System Controller


Issue 3 October 2011

165

This report gives the start date, start time, start reason, stop reason, and boost duration in
minutes. The start reasons are:
MANUALBoost initiated by user
AUTOBoost started automatically after a battery discharge
RESUMEDBoost resumed after being suspended by a discharge

The stop reasons are:
COMPLETEDBoost completed normally
TIMEOUTBoost timed out before completing
DISCHARGEBoost suspended because of a battery discharge
CANCELEDBoost canceled by user
ALARMBoost cancelled by an alarm condition
DISABLEDAuto boost cancelled by being disabled

his

Report BD History

Syntax:

dc1,bod

Description
This command reports the battery discharge history in the following format:
his dc1,bod
30-MAY-03,15:11:12,MANUAL,COMPLETED,118.3,23,
01-APR-03,03:11:12,BD,COMPLETED,118.3,26,130
12-FEB-03,12:00:02,PERIODIC,COMPLETED,120.9,27,135
.
**

This report gives the start date, start time, start reason, current at start of discharge, duration in
minutes, and, if calculated, a reserve time prediction. The start reasons are:

MANUALDischarge test initiated by user
PERIODICPeriodic discharge test
BDNatural battery discharge

The stop reasons are:

COMPLETEDDischarge completed normally
TIMEOUTAuto discharge test timed out
DISABLEDAuto discharge test disabled
ENDVDischarge test hit end voltage
CANCELEDDischarge test canceled by user

lis

List Rectifiers

Syntax:

lis rec

Description