Galaxy Pulsar Edge Power System Controller


Issue 3 October 2011

67


LVBD

Provides LVBD (Low Voltage Battery Disconnect) status. “None” is
displayed for each non-configured contactor. “Closed” is shown for
normal contactor state. “Open” shown for contactors that have opened
and disconnected the battery. The summation of all shunts monitored by
distribution monitoring boards ID1-ID8 that are assigned to battery or
load current is shown. Configuring the centralized plant shunt as a
battery shunt will also be the value shown here.

LVLD(1-3)

Provides the status of the three LVLDs (Low Voltage Load Disconnects
1-3). “None” is displayed for each non-configured contactor. “Closed”
is shown for normal contactor state. “Open” will be shown for
contactors that have opened or disconnected each respective load. The
summation of all shunts monitored by distribution monitoring boards
ID1-ID8 that are assigned to each specific LVLD is summed and shown
for its respective assignment.

Pulsar Edge/System

This section provides the high level view of the power system states which includes the
items shown below.