Galaxy Pulsar Edge Power System Controller


Issue 3 October 2011

188

Factory Default

Factory 24V

Rectifier Default

Factory 48V

Rectifier

Default

Category

Description

Range

Factory

Factory 24V

Factory 48V

obj,attr

Auxiliary Alarm 5 Front Panel Desc

<=24 chars

"Low Ext Ambient"

AUX5,FDS

Auxiliary Alarm 6 Description

<=32 chars

"Fan Fail"

AUX6,DES

Auxiliary Alarm 6 Front Panel Desc

<=24 chars

"Fan Fail"

AUX6,FDS

Auxiliary Alarm 7 Description

<=32 chars

"Hydrogen Present"

AUX7,DES

Auxiliary Alarm 7 Front Panel Desc

<=24 chars

"Hydrogen Present"

AUX7,FDS

Auxiliary Alarm 8 Description

<=32 chars

"Customer Alarm 1"

AUX8,DES

Auxiliary Alarm 8 Front Panel Desc

<=24 chars

"Customer Alarm 1"

AUX8,FDS

Auxiliary Alarm 9 Description

<=32 chars

"Customer Alarm 2"

AUX9,DES

Auxiliary Alarm 9 Front Panel Desc

<=24 chars

"Customer Alarm 2"

AUX9,FDS

Auxiliary Alarm 10 Description

<=32 chars

"Customer Alarm 3"

AUX10,DES

Auxiliary Alarm 10 Front Panel
Desc

<=24 chars

"Customer Alarm 3"

AUX10,FDS

Auxiliary Alarm 11 Description

<=32 chars

"Customer Alarm 4"

AUX11,DES

Auxiliary Alarm 11 Front Panel
Desc

<=24 chars

"Customer Alarm 4"

AUX11,FDS

Auxiliary Alarm 12 Description

<=32 chars

"Customer Alarm 5"

AUX12,DES

Auxiliary Alarm 12 Front Panel
Desc

<=24 chars

"Customer Alarm 5"

AUX12,FDS

Alarm Test

Alarm Test Enable

1=Enabled

0=Disabled

1

AT1,LTE

Duration of Each Relay Closure

5 to 300 sec

30

AT1,DUR

PMJ Relay Test Enable

1=Enabled

0=Disabled

1

AT1,PMJ

PMN Relay Test Enable

1=Enabled

0=Disabled

1

AT1,PMN

R1 Relay Test Enable

1=Enabled

0=Disabled

1

AT1,R1

R2 Relay Test Enable

1=Enabled

0=Disabled

1

AT1,R2

R3 Relay Test Enable

1=Enabled

0=Disabled

1

AT1,R3

Serial Communication

Ports

Communication Port Type

LOCAL or

MODEM

"LOCAL"

PS1,PTT

Local Port Write Access

1=Enabled

0=Disabled

1

LP1,WRE

Local RS-232 baud rate

2400/4800/ 9600/

Auto

"AUTO"

LP1,BDR

Local RS-232 handshaking (Flow
Control)

No/SW/HW

"NO"

LP1,HSH

Number of Local RS-232 data bits

7,8

8

LP1,DBT

Local RS-232 parity

n,e,o

N

LP1,PRY

Number of Local RS-232 stop bits

1,2

1

LP1,SBT

Local RS-232 Time-out

0-45 minutes

5

LP1,TMO

Local RS-232 Application

TERMINAL,

EVENT LOG

"TERMINAL"

LP1,APP

Modem Port Write Access

1=Enabled

0=Disabled

1

MP1,WRE

Modem baud rate

2400/4800/ 9600

"2400"

MP1,BDR

Number Of Modem data bits

7,8

8

MP1,DBT

Modem parity

n,e,o

N

MP1,PRY

Number Of Modem stop bits

1,2

1

MP1,SBT