GE Industrial Solutions Galaxy Pulsar Edge User Manual

Page 183

Advertising
background image

Galaxy Pulsar Edge Power System Controller


Issue 3 October 2011

183

Factory Default

Factory 24V

Rectifier Default

Factory 48V

Rectifier

Default

Category

Description

Range

Factory

Factory 24V

Factory 48V

obj,attr

Daylight Saving End

mon:wk:dow:min

mon:-1:dom:min

"11:1:0:120"

PS1,DSE

Time zone offset

-840 - +840

minutes (±14

hours)

0

PS1,TZO

Uninstall Equipment Timeout

0 to 60s

15

PS1,UET

Critical Equals Major

1=Enabled

0=Disabled

1

PS1,CEM

User Password

"lineage"

PAS U,

Super-user Password

"super-user"

PAS S,

Administrator Password

"administrator"

PAS A,

Low Voltage Disconnects

Battery Disconnect 1

Battery Disconnect Control Mode

0=none,

1=voltage

2=voltage/time,

3=adaptive

1

CN1,DAM

Battery Disconnect Time Delay

0:0:0 to 4:59:59

0:00:00

CN1,DDY

Battery Reconnect Control Mode

0=none,

1=voltage

2=voltage/time

1

CN1,RAM

Battery Reconnect Time Delay

0 to 300 sec

0

CN1,RDY

Battery Disconnect Description

<=32 Chars

"LVBD"

CN1,DES

Battery Disconnect Open
Description

<=32 Chars

"LVBD Open"

CNO1,DES

Battery Disconnect Open Front
Panel Description

<=32 Chars

"LVBD Open"

CNO1,FDS

Battery Disconnect Failed
Description

<=32 Chars

"LVBD Failed"

CNF1,DES

Battery Disconnect Failed Front
Panel Description

<=32 Chars

"LVBD Failed"

CNF1,FDS

Load Disconnect 1

Load 1 Disconnect

1=Enabled

0=Disabled

0

CN2,ENA

Load 1 Disconnect Control Mode

0=none,

1=voltage

2=voltage/time

1

CN2,DAM

Load 1 Disconnect Voltage

19.5 to 25V

-39.0 to -50V

21.50

43.00

CN2,DTH

Load 1 Disconnect Time Delay

0:0:0 to 4:59:59

0:00:00

CN2,DDY

Load 1 Reconnect Control Mode

0=none,

1=voltage

2=voltage/time

1

CN2,RAM

Load 1 Reconnect Voltage

19.5 to 27

-39.0 to -55.0V

22.00

44.00

CN2,RTH

Load 1 Reconnect Time Delay

0 to 300 sec

0

CN2,RDY

Load 1 Disconnect Description

<=32 Chars

"LVLD1"

CN2,DES

Load 1 Disconnect Open
Description

<=32 Chars

"LVLD1 Open"

CNO2,DES

Load 1 Disconnect Open Front Panel
Description

<=32 Chars

"LVLD1 Open"

CNO2,FDS

Load 1 Disconnect Failed
Description

<=32 Chars

"LVLD1 Failed"

CNF2,DES

Load 1 Disconnect Failed Front
Panel Description

<=32 Chars

"LVLD1 Failed"

CNF2,FDS

Load Disconnect 2

LV Load 2 Disconnect

1=Enabled

0=Disabled

0

CN3,ENA

LV Load 2 Disconnect Control
Mode

0=none,

1=voltage

2=voltage/time

1

CN3,DAM

LV Load 2 Disconnect Voltage

19.5 to 25V

-39.0 to -50V

21.00

42.00

CN3,DTH

LV Load 2 Disconnect Time Delay

0:0:0 to 4:59:59

0:00:00

CN3,DDY

LV Load 2 Reconnect Control Mode

0=none,

1=voltage

2=voltage/time

1

CN3,RAM