Galaxy Pulsar Edge Power System Controller


Issue 3 October 2011

103

the Pulsar Edge’s port to be configured to operate plugged into the
network.

It can also be used in a “DHCP- Server” mode to provide Craft port
functionality. In this mode the Pulsar Edge up 192.168.2.1 which
should be used as the destination address in a user’s browser. Note:
once this parameter is changed, the controller must be re-booted by
removing power from the unit by removing and re-inserting the unit
into the shelf.

IP Address

*

Internet Protocol address (Static) assigned to the Pulsar Edge that
identifies the unit on the network. The format for the IP address field
is a 32-bit numeric address written as four numbers separated by
periods (ddd.ddd.ddd.ddd). Each number, ddd, can be 0 to 255. In the
server mode, 192.168.2.1 shall be used to access the controller.

Subnet Mask

*

Internal network address assigned for identifying an internal network
mask that the Pulsar Edge has been assigned to by a network
administrator. The mask selectively includes or excludes certain
equipment on a Host. The format for the Subnet Mask field is a 32-bit
numeric address written as four numbers separated by periods
(ddd.ddd.ddd.ddd). Each number, ddd, can be 0 to 255.

Default Router
Gateway

*

This address is for the address of the Gateway or node on the network
that will serve as the entrance to another network for the Pulsar Edge.
This address should be the address of the equipment or computer that
routes the traffic from and to the Pulsar Edge to the outside network. It
is generally the proxy server. The format for the Gateway address field
is a 32-bit numeric address written as four numbers separated by
periods (ddd.ddd.ddd.ddd). Each number, ddd, can be 0 to 255.

Domain Name
DNS

*

Address of the Domain Name Server that translates domain names into
IP addresses. This field is of the format ddd.ddd.ddd.ddd.

Host Name

Network name assigned and configured for the Pulsar Edge since it
acts as a repository for data and services such as e-mail, FTP, HTTP,
etc that are accessed remotely by other equipment or users on the
network.

Mail Host
(Server)

The address for the computer or equipment within the network that
will manage the Pulsar Edge e-mails. The format for the Gateway
address field is a 32-bit numeric address written as four numbers
separated by periods (ddd.ddd.ddd.ddd). Each number, ddd, can be 0
to 255. If configured as 0.0.0.0, the controller will use the hostname
mail host.

Session Timeout

Configured time that the controller will hold a static network
connection before disconnecting. This time is configurable between 0
and 45 minutes. A “0” is a non-timed connection. The factory default
is 10 minutes.

Write Enabled

This field shows whether the port has been configured to allow
Read/Write access or Read Only access. Read/Write access is
available when the feature has been enabled.