Temperature alarms – GE Industrial Solutions Galaxy Pulsar Edge User Manual
Page 172
Galaxy Pulsar Edge Power System Controller
Issue 3 October 2011
172
Figure C-1: Slope Thermal Compensation
The following describes the configuration parameters which may be Enabled/Disabled and
configured by the user. Refer to Appendix D for the ranges of values the parameters may take and
their factory default settings.
Temperature Alarms
The Pulsar Edge has several alarm thresholds that can be set based on temperature.
• High Temperature Alarm: The High Battery Thermal Alarm Threshold (thr) is
the monitored battery temperature at which above this threshold results in a High
Battery Thermal alarm. This alarm threshold can be set from 30°C to 85°C and its
severity is configurable. The alarm retires when the temperature drops to 10°C
below the set threshold. The factory default setting is 55°C with Power Minor