Figure C-1: Slope Thermal Compensation

The following describes the configuration parameters which may be Enabled/Disabled and
configured by the user. Refer to Appendix D for the ranges of values the parameters may take and
their factory default settings.

Temperature Alarms

The Pulsar Edge has several alarm thresholds that can be set based on temperature.

High Temperature Alarm: The High Battery Thermal Alarm Threshold (thr) is

the monitored battery temperature at which above this threshold results in a High
Battery Thermal alarm. This alarm threshold can be set from 30°C to 85°C and its
severity is configurable. The alarm retires when the temperature drops to 10°C
below the set threshold. The factory default setting is 55°C with Power Minor