9 Troubleshooting

Table 9-A: Power System Troubleshooting Table

Controller

LED

User Interface

Display

Rectifier

LED

Distribution

Module

Board LED

Possible Problem(s)

Possible Solution(s)

AMBER

MIN, AC Fail

None

GREEN

Single Rectifier not
receiving ac power.

AC input circuit breaker
has opened.

AC input voltage is out
of range

.

1. Verify ac power to rectifier is

available.

2. Verify rectifier input circuit

breaker is closed.

3. If problem not corrected,

replace rectifier.

RED

MIN, AC Fail

MAJ, Multiple
AC Fail

MAJ, Battery on
Discharge

None

GREEN

Multiple rectifiers not
receiving ac power,
batteries are powering
load.

AC input circuit
breakers have opened.

AC input voltage is out
of range.

Internal rectifier fault.

1. Verify ac power to rectifiers is

available.

2. Verify rectifier input circuit

breakers are closed.

3. If problem not corrected,

replace rectifier.

AMBER

or

RED

MIN, AC Fail

MAJ, Multiple
AC Fail

None

GREEN

A rectifier, multiple
rectifiers, or the entire
system has lost AC and
one or more rectifiers have
been removed from the
system while under this
condition.

1. Verify that ac power to all

rectifiers is available.

2. Verify that rectifiers all report

good AC

3. Issue the uninstall equipment

under the operations menu for
any rectifier that may have been
removed during the AC fail.

RED

MAJ, Battery on
Discharge

AC OK

DC OK

GREEN

Rectifier output voltage
has fallen below the
battery on discharge
threshold set by the user.

1.

If commercial ac power is
present but the system voltage
remains low, call your local
field representative.

2.

Investigate other alarms that
may be present such as
rectifier related problems.

AMBER

MIN, Rectifier
Fail (Note 1)

AC OK

ALARM

(Note 1)

GREEN

Rectifier output has
dropped below 36V,
rectifier has entered hiccup
mode.

Replace rectifier.

RED

MAJ, Rectifier
Fail

AC OK

ALARM

(Note 1)

GREEN

All rectifier outputs have
dropped below 36V, all
rectifiers have entered
hiccup mode.

Defective controller.

Remove controller; if output
voltage does not go to set-point
previously set by user, call your
local field representative.