Galaxy Pulsar Edge Power System Controller


Issue 3 October 2011

75

System Maintenance Operations

Lamp Test

Temporarily illuminates all status indicators of attached rectifiers,
distribution monitoring and control modules and the system controller.

Restart Rectifiers

Provides the ability to restart all system serial controlled rectifiers at
once. This operation does not affect rectifiers and other system devices
that are already functioning.

Restart Converters

Provides the ability to restart all system serial controlled converters at
once. This operation does not affect converters and other system
devices that are already functioning.

Boost

Initiates the manual battery Boost feature. A stop battery Boost
operation is displayed to interrupt the Boost operation mode and return
the unit to normal operation.

Start Battery Test

Initiates the manual battery test feature. A stop battery test operation is
displayed to interrupt the testing and return the unit to normal
operation. The manual battery test utilizes the configured test duration
and a system bus voltage threshold to represent the end of reserve.

Start Alarm Test

Provides ability to initiate an alarm test on a specific user selected
output relay or all output relays. Alarm relays are asserted at the
configured alarm interval.

Start SNMP Trap
Test

Provides ability to generate the configured SNMP traps all at once
without having to actually generate the specific system alarm
condition. All assigned traps are sent out at once.

Remote Standby

Allows a remote user to place a designated group of rectifiers all into
Standby when the Remote Group Standby feature is enabled.

Load Defaults

This operation allows a user to bring back all factory default settings
and configurations with a single operation. Factory defaults are also
custom configuration defaults when they are available. Custom
configurations may support multiple factory defaults. Caution must be
used when applying this command. Previous configuration changes
made in the field will be overwritten with the factory values.

Clear Data Maintenance Operations

Reset Reserve Time

Resets any reserve time calculations or prediction data to allow the
system a new starting point.

Clear Missing
Devices

Clears alarms related to the removal of a system component such as a
rectifier, thermal probe, or voltage monitoring module. Running this
command allows the system controller to retake inventory of using
equipment over the various digital communication busses.

Clear Latched
Events

Used to clear momentary events or alarms that are latched by the
Pulsar Edge. It clears the following system alarms: Check Battery,
Reserve Time Low, Real-Time Reserve Low, Battery Voltage
Imbalance, External Password Reset, Excessive Login Attempts,
Clock Changed, Self Test Failed, Configuration Changed, History
Cleared, Incompatible Rectifier, Incompatible Converter, Queue
Overflow, No Call-Out Response, No Dial-Out Response, Alarm Test