Micromod RetroPAK: SLC Configuration Manual User Manual
Page 122
Advertising
Command Series Migration to MOD 30ML
Pre-configured Dual Loop PID Control
To enable Setpoint Tracking (FC21-S14):
Open the PID block and open the Options tab. Check the box Enable Setpoint Tracking.
Connect a setpoint tracking input to the SPTI attribute of the PID block.
See figure below:
Dual loop
PID with Local SP
P2- 16
Advertising
This manual is related to the following products: