Micromod RetroPAK: SLC Configuration Manual User Manual

Page 151

Advertising
background image

Command Series Migration to MOD 30ML

Pre-configured Dual Loop PID with Remote SP


To configure the inputs:

Open the AIN block AIN1 for input 1. See figure below:

Figure P4.2.

Dual PID with
Remote SP

You can change the Input Type and Linearization Type for the built-in input 1 here.
Specify the Input Signal Range also.

The VCI block ENG UNITS 1 in the loop compound is used for converting the voltage,
millivolts or current input signal to engineering units. See figure below:

Change the Linearization type (Linear, Square, Square root, Modified Square, Modified
Square root) as required for the input signal and specify the Engineering Range and
Quality Limits.

P4- 5