Command Series Migration to MOD 30ML
Pre-configured Dual Loop PID with Remote SP
To change the value of the Output Limits (S16, S17):
Open the PID block and open the Output tab. Change the values for the Output Limits –
Low and High and Output range – Low and High.
See figure below:
Dual PID with
Remote SP
P4- 14