Command Series Migration to MOD 30ML

Function Code 156 – PID with Manual/Auto Station

S12

M/A

Input – GAIN
Floating Point

Proportional Gain Kp. Enter in the M/A
block under the General tab.

S13

M/A

Input – RESET
Floating Point

Integral Reset in resets/min (RPM) Ki.
Enter in the M/A block under the General
tab.

S14

M/A

Input – PREACT
Floating Point

Derivative rate in minutes Kd. Enter in the
M/A block under the General tab.

S15

M/A

Input – Floating
Point

Derivative Lag constant Ka. Enter the
value in the PID block. Open the Control
tab and change the INPUT FILTER TPE
to PRE-ACT USER and type the value in
the INPUT FILTER TIME field.

S16

M/A

Input – Floating
Point

High Output Limit. Enter the value in the
PID block. Open the Output tab and
change the OUTPUT LIMITS HIGH
field and OUTPUT RANGE HIGH field.

S17

M/A

Input – Floating
Point

Low Output Limit. Enter the value in the
PID block. Open the Output tab and
change the OUTPUT LIMITS LOW
field and OUTPUT RANGE LOW field.

S19 N/A

N/A

N/A

S19 N/A

N/A

N/A

S21

M/A

Input – Discreet

Controller Action. Choose the action in
the PID block. Open the General tab and
select the desired CONTROLLER
ACTION
.

N

M/A

Output – N
Floating Point

Output of the compound. Connect from
the M/A.N signal of the compound.

156ma - 3