Command Series Migration to MOD 30ML

Function Code 156 – PID (Cascade)


To change the values of the following:

Proportional Gain - S12

Integral Reset – S13

Derivative Rate – S14

To enter a local value, open the ENG function block (Expression block) and select the
Inputs tab. Double click on the number next to the desired input GAIN_1, GAIN_2,
GAIN_F, RESET_1, RESET_2, RESET_F, PREACT_1, PREACT_2, PREACT_F) and
change the value.

See figure below:

Figure 156c .6.

Function Code
156

Cascade PID

156c - 9