Micromod RetroPAK: SLC Configuration Manual User Manual
Page 382
Advertising
Command Series Migration to MOD 30ML
Function Code 156 – Auto Bias Station
To change the values of the following:
Proportional Gain - S12
Integral Reset – S13
Derivative Rate – S14
To enter a local value, open the PID block and select the General tab. Type values for
Base Gain – Base Value, enable the Base Reset Rate and Base Pre-act Time and type
value for the Base Values.
See figure below:
Function Code
156
Auto Bias Station
156ab - 8