Command Series Migration to MOD 30ML

Pre-configured PID Ratio with Remote SP


To connect / change the value of the Gain Multiplier input (S11):

Make a connection into the PID.S11 signal of the compound.

To enter a local value, open the respective PID block and select the Control tab. Check
the Internal checkbox in the Gain Multiplier Input field and enter a value in the value
in the text field. See the next figure:

Figure P6.6.

PID Ratio with
Remote SP

P6- 9