Command Series Migration to MOD 30ML

Function Code 9 – Analog Transfer

S2

S1/S2

Input – S2
Floating Point

Connect to the S1/S2.S2 signal
of the compound.

S3

S3

Input – S3
Boolean
(Discrete)

Connect to the S3.S3 signal of
the compound.

S4

S4

Input – S4 Milli-
second time

Enter value in Milli-second time
in the Timer Limits High field

S5

S5

Input – S5 Milli-
second time

Enter value in Milli-second time
in the Timer Limits High field

SCAN

FC9

Input – SCAN

Enter controller scan time value
in floating point units in the
SCAN field. For example 0.25
for 250 ms.

N

FC9

Output – R
Floating Point

Connect from the FC9.N signal
of the compound. Output from
the FC9 block is the result of the
calculation.

NOTES

Execution Order:

The function blocks S1/S2,S3,FC9 and LAST INPUT in this compound need to be
executed in the following order:

S1/S2

S3

FC9

LAST INPUT

To verify this, check the execution order of the blocks. Select Objects – Set Execution
Order – List Mode
from the menu bar. The Execution Order dialog will be displayed as
shown in the next figure:

9 - 2