Command Series Migration to MOD 30ML

Pre-configured PID Ratio with Remote SP


To change the process variable high alarm (FC21-S7):

Open the PAD block HIGH ALARM. Change the value of the Trip Value by typing.

See figure below:

Figure P6.16.

Process Variable
High Alarm

PID Ratio with
Remote SP

P6- 19