Command Series Migration to MOD 30ML

Pre-Configured – Cascade Control


To configure the inputs:

Open the AIN block AIN1 for input 1. See figure below:

Figure P5.2.

Cascade PID

You can change the Input Type and Linearization Type for the built-in input 1 here.
Specify the Input Signal Range also.

The VCI block ENG UNITS 1 in the loop compound is used for converting the voltage,
millivolts or current input signal to engineering units. See figure below:

Change the Linearization type (Linear, Square, Square root, Modified Square, Modifed
Square root) as required for the input signal and specify the Engineering Range and
Quality Limits.

P5- 5