Command Series Migration to MOD 30ML

Pre-configured Single Loop PID with Remote SP

EXPLANATION

Configuration with this compound requires understanding of the compound and how the
PID block is configured in the MOD 30ML/Modcell controllers. Following is the
reference that includes listing of most commonly used / changed attribute and inputs and
outputs. Necessary block configuration tabs are also explained to make it easier.

INPUTS - OUTPUTS

Signal Block

Type

Description

S1

PID

Input – S1
Floating Point

Result (R) of the VCI block VCI1 is
already connected to PID.S1 signal of
the compound for the first loop.

Process Input signal.

S1Q

QUALLOGIC

Output – S1Q
Boolean (Discrete)

Connect to the QUALLOGIC.S1Q
signal of the compound. Process Input
Quality

S2

PID

Input – S2
Floating Point

Result (R) of the VCI block VCI2 is
already connected to PID.S2 signal of
the compound for the first loop.

Remote Setpoint signal.

S3

PID

Input – S3
Floating Point

Connect to the PID.S3 signal of the
compound. Track Reference.

S4

PID

Input – S4
Boolean

Connect to the PID.S4 signal of the
compound. Track Switch.

S5

PID

Input – Floating
Point

Change in the Control tab of the
corresponding PID block. Change the
value for MANUAL RESET – BASE
VALUE.

S6

PID

Input – S6
Floating Point

Feed-forward input for the PID. Enable
in the Options tab of the PID block.
Change the calculation type to Add.
Connect the feed forward input to the
PID.S6 signal of the compound.

S7 N/A

N/A

N/A

S8 N/A

N/A

N/A

S9 N/A

N/A

N/A

S10 N/A

N/A

N/A

S11

PID

Input – S11
Floating Point

Gain Multiplier input for the PID.
Connect to the PID.S11 signal of the

P3 - 2