Command Series Migration to MOD 30ML
Pre-configured PID Ratio with Remote SP
To enable Setpoint Tracking (FC21-S14):
Open the PID block and open the Options tab. Check the box Enable Setpoint Tracking.
Connect a setpoint tracking input to the SPTI attribute of the PID block.
See figure below:
PID Ratio with
Remote SP
P6- 16