Micromod RetroPAK: SLC Configuration Manual User Manual

Page 171

Advertising
background image

Command Series Migration to MOD 30ML

Pre-Configured – Cascade Control


GAIN MULTIPLIER INPUT.

S11

PID2

Input – S11
Floating Point

Gain Multiplier input for the PID2.
Connect to the PID2.S11 signal of the
compound or change in the Control tab
of the PID2 block. Change the value for
GAIN MULTIPLIER INPUT.

S11

PIDFAIL

Input – S11
Floating Point

Gain Multiplier input for the failover
PID (PIDFAIL). Connect to the
PIDFAIL.S11 signal of the compound
or change in the Control tab of the
PIDFAIL block. Change the value for
GAIN MULTIPLIER INPUT.

S12

ENG

Input – GAIN_1,
GAIN_2, GAIN_F
Floating Point

Proportional Gain Kp. Enter in the ENG
block. Open the Inputs tab and select the
respective input (GAIN_1, GAIN_2,
GAIN_F
) to change the value.

S13

ENG

Input – RESET_1,
RESET_2,
RESET_F Floating
Point

Integral Reset in resets/min (RPM) Ki.
Enter in the ENG block. Open the
Inputs tab and select the respective input
(RESET_1, RESET_2, RESET_F) to
change the value.

S14 ENG

Input

PREACT_1,
PREACT_2,
PREACT_F
Floating Point

Derivative rate in minutes Kd. Enter in
the ENG block. Open the Inputs tab and
select the respective input (PREACT_1,
PREACT_2, PREACT_F
) to change
the value.

S15 PID1,

PID2,

PIDFAIL

Input – S15
Floating Point

Derivative Lag constant Ka. Enter the
value in the respective PID block. Open
the Control tab and change the INPUT
FILTER TPE
to PRE-ACT USER and
type the value in the INPUT FILTER
TIME
field.

S16 PID1,

PID2,

PIDFAIL

Input – S16
Floating Point

High Output Limit. Enter the value in
the respective PID block. Open the
Output tab and change the OUTPUT
LIMITS HIGH
field and OUTPUT
RANGE HIGH
field.

S17 PID1,

PID2,

PIDFAIL

Input – S17
Floating Point

Low Output Limit. Enter the value in
the respective PID block. Open the
Output tab and change the OUTPUT
LIMITS LOW
field and OUTPUT
RANGE LOW
field.

P5- 3