Inputs - outputs – Micromod RetroPAK: SLC Configuration Manual User Manual

Page 346

Advertising
background image

Command Series Migration to MOD 30ML

Function Code 156 – PID Ratio with Remote SP

reference that includes listing of most commonly used / changed attribute and inputs and
outputs. Necessary block configuration tabs are also explained to make it easier.

INPUTS - OUTPUTS

Signal Block

Type

Description

S1

PID

Input – S1
Floating Point

Connect to the PID.S1 signal of the
compound. Process Input signal.

S1Q

QUALLOGIC

Output – S1Q
Boolean (Discrete)

Connect to the QUALLOGIC.S1Q
signal of the compound. Process Input
Quality

S2

PID

Input – S2
Floating Point

Connect to the PID.S2 signal of the
compound. Remote Setpoint signal.

S3

PID

Input – S3
Floating Point

Connect to the PID.S3 signal of the
compound. Track Reference.

S4

PID

Input – S4
Boolean

Connect to the PID.S4 signal of the
compound. Track Switch.

S5

PID

Input – Floating
Point

Change in the Control tab of the
corresponding PID block. Change the
value for MANUAL RESET – BASE
VALUE.

S6

PID

Input – S6
Floating Point

Feed-forward input for the PID. Enable
in the Options tab of the PID block.
Change the calculation type to Add.
Connect the feed forward input to the
PID.S6 signal of the compound.

S7 N/A

N/A

N/A

S8 N/A

N/A

N/A

S9 N/A

N/A

N/A

S10 N/A

N/A

N/A

S11

PID

Input – S11
Floating Point

Gain Multiplier input for the PID.
Connect to the PID.S11 signal of the
compound or change in the Control tab
of the PID block. Change the value for
GAIN MULTIPLIER INPUT.

S12

ENG

Input – GAIN
Floating Point

Proportional Gain Kp. Enter in the ENG
block. Open the Inputs tab and select
GAIN to change the value.

S13

ENG

Input – RESET

Integral Reset in resets/min (RPM) Ki.
Enter in the ENG block. Open the

156rr - 2

Advertising