Function Code 33 – NOT

GENERAL DESCRIPTION

Function code 33 performs a logical negation of the input (the output is the opposite of
the input).

UTILIZATION

The MOD 30ML/MODCELL compound FC33 used here has an EX function block
(Expression block).

Figure 33 .1.

Function Code 33

The EX block has one input S1 that need to be connected to the attribute that needs a
logical negation.

INPUTS - OUTPUTS

Signal

Block

Type

Description

S1

FC33

Input – S1
Floating Point

Connect to the FC33.S1 signal of the
compound. Input to the NOT function.

N

FC33

Output – R
Floating Point

Connect from the FC33.N signal of the
compound. Result of the logic.

33 - 1