Page 155
Advertising
Command Series Migration to MOD 30ML
Pre-configured Dual Loop PID with Remote SP
To enable feedforward control and change the feedforward type (S6):
Open the PID block and select the Options tab. See figure below:
Dual PID with
Remote SP
Connect the desired signal to the feedforward input (PID.S6) of the compound.
P4- 9